MPI-530 Multifunction Electrical Installations Meter

Availability:

1 in stock


 

  • Short circuit loop impedance (also in circuits secured with RCDs)
  • RCD parameters
  • Insulation resistance
  • Earth resistance (4 measurement methods + soil resistivity measurement)
  • Continuity of protective and equipotential bondings
  • Light intensity measurement
  • Phase sequence test
  • Motor rotation direction test.

264,000.00  288,500.00 

1 in stock

*

Product Description

The multifunctional meter of parameters of electrical installations Sonel MPI-530 is used for precise measurements of electrical installations. The device has been constructed in compliance with the requirements of the EN 61557 standard. It makes it possible to carry out all measurements connected with protection against electric shock described in the HD 60364-6 standard.

The Sonel MPI-530 specialized meter is distinguished by extensive ground measurement functions – additional clamp methods and soil resistivity. Using the optional AuroISO-1000C adapter, automatic insulation resistance measurements are also possible in sockets and for 3-, 4- and 5-core cables.

With the use of the Sonel MPI-530 meter, it is also possible to test the illumination intensity. An additional external probe is required for this purpose. The instrument can record and analyze network parameters – including harmonics up to 40th. Another advantage of the meter is the robust IP54 casing, which protects the device from mechanical damage, dust, or splashing.

Technical data

Measurement functions

Measurement range

Display range

Resolution

Accuracy

Fault loop impedance

Fault loop ZL-PE, ZL-N, ZL-L

0.13 Ω…1999.9 Ω acc. to IEC 61557

0.00 Ω…1999 Ω

from 0.001 Ω

±(5% m.v. + 30 digits)

Fault loop ZL-PE in RCD mode

from 0.50 Ω…1999 Ω acc. to IEC 61557

0.00 Ω…1999 Ω

from 0.01 Ω

from ±(6% m.v. + 5 digits)

Measurements of RCD parameters

general and short-time delay RCD

TN / TT mains

0 ms…300 ms

0 ms…300 ms

1 ms

±(2% m.v. + 2 digits)

selective RCD

0 ms…500 ms

0 ms…500 ms

1 ms

from ±(2% m.v. + 2 digits)

Measurement of RCD tripping current IA measuring current 0.2 IΔn…2.0 IΔn

for sinusoidal residual current (AC type)

3.3 mA…1000 mA

3.3 mA…1000 mA

from 0.1 mA

±5% IΔn

for unidirectional residual current and unidirectional with the 6 mA DC bias (type A)

3.5 mA…700 mA

3.5 mA…700 mA

from 0.1 mA

±10% IΔn

for direct residual current
(type B))

2.0 mA…1000 mA

2.0 mA…1000 mA

from 0.1 mA

±10% IΔn

Earth resistance

3- and 4-pole method

from 0.50 Ω…1.99 kΩ acc. to IEC 61557-5

0.00 Ω…1,99 kΩ

from 0.01 Ω

from ±(2% m.v. + 3 digits)

3-pole + clamp method

0.00 Ω…1.99 kΩ

0.00 Ω…1.99 kΩ

from 0.01 Ω

±(8% m.v. + 4 digits)

2-clamp method

0.00 Ω…99.9 kΩ

0.00 Ω…99.9 kΩ

from 0.01 Ω

from ±(10% m.v. + 4 digits)

Resistance-to-earth

0.0 Ω m…99.9 kΩm

0.0 Ωm…99.9 kΩm

from 0.1 Ωm

Depending on accuracy of RE measurement

Insulation resistance

Measuring voltage 50 V

50 kΩ…250 MΩ acc. to IEC 61557-2

0 kΩ…250 MΩ

from 1 kΩ

from ±(3% m.v. + 8 digits)

Measuring voltage 100 V

100 kΩ…500 MΩ acc. to IEC 61557-2

0 kΩ…500 MΩ

from 1 kΩ

from ±(3% m.v. + 8 digits)

Measuring voltage 250 V

250 kΩ…999 MΩ acc. to IEC 61557-2

0 kΩ…999 MΩ

from 1 kΩ

from ±(3% m.v. + 8 digits)

Measuring voltage 500 V

500 kΩ…2.00 GΩ acc. to IEC 61557-2

0 kΩ…2.00 GΩ

from 1 kΩ

from ±(3% m.v. + 8 digits)

Measuring voltage 1000 V

1000 kΩ…4.99 GΩ acc. to IEC 61557-2

0 kΩ…9.99 GΩ

from 1 kΩ

from ±(3% m.v. + 8 digits)

Resistance of protective conductors and equipotential bondings

Measurement of resistance of protective conductors and
equipotential bondings with ±200 mA current

0.12 Ω…400 Ω acc. to IEC 61557-4

0.00 Ω…400 Ω

from 0.01 Ω

±(2% m.v. + 3 digits)

Measurement of resistance with low current

0.0 Ω…1999 Ω

0.0 Ω…1999 Ω

from 0.1 Ω

±(3% m.v. + 3 digits)

Light intensity

Measurement in luxes (lx)

0 lx…399.9 klx

0 lx…399.9 klx

from 0.001 lx

from ±(2% m.v. + 5 digits)

Measurement in feet-candles (fc)

0 fc…39.99 kfc

0 fc…39.99 kfc

from 0.001 fc

from ±(2% m.v. + 5 digits)

Downloads

Datasheet : MPI-530

Instruction Manual : MPI-530

Videos

 

Unbox : MPI-530