Dark Light
-10%
,

Fluke 1503 Insulation Resistance Meter

Availability:

33 in stock


  • A rugged, compact insulation resistance tester for residential and commercial electricians
  • Performs insulation tests from 0.01 MΩ to 2000 MΩ
  • Offers two insulation test voltages: 500 V and 1000 V
  • Includes live circuit detection to prevent insulation test if voltage >30 V is detected
  • Measures resistance from 0.01 Ω to 20.00 kΩ

48,420.00  53,800.00 

33 in stock

*

Product Description

Fluke 1503 Insulation Resistance Tester handles all the basic insulation testing needs

The Fluke 1503 is a great choice for basic residential and commercial electrical insulation testing. This rugged, compact tool fits in the palm of your hand. The 1503 is the same form factor as the Fluke 1507 but with a few less features. You can count on it to handle the most common tests at a most affordable price. Additional features, like the remote probe, reduce the time needed to perform repetitive testing.

Other useful capabilities:

  • Measures AC/DC voltage from 0.1 V to 600 V
  • Includes auto-discharge of capacitive voltage for added user protection
  • Provides lo-ohms earth-bond continuity (200 mA)
  • Simplifies repetitive or hard-to-reach testing with the remote test probe
  • Saves battery power with auto power off
  • Presents results on a large, backlit display
  • Features CAT IV 600 V overvoltage category rating
  • Comes with remote probe, test leads, test probes, alligator clips, and one-year warranty
  • Accepts optional Fluke TPAK magnetic hanging system to free your hands for other work
  • Runs on four AA alkaline batteries (NEDA 15 A or IEC LR6) for at least 1000 insulation tests

Technical data

General Specifications

General Specifications

Specifications

AC/DC Voltage Measurement

Range 600.0 V
Resolution 0.1 V
50 Hz to 400 Hz ±(% of Rdg + Digits) ±(2% + 3)

Input impedance

3 MΩ (nominal), < 100 pF

Common mode rejection ratio (1 kΩ unbalanced)

> 60 dB at DC, 50 or 60 Hz

Overload protection

600 V rms or DC

Earth Bond Resistance Measurement

Range/Resolution

20.00 Ω 0.01 Ω
200.0 Ω 0.1 Ω
2000 Ω 1.0 Ω
20.00 kΩ 0.01 kΩ

Accuracy

±(1.5% + 3)

Overload protection

2 V rms or DC

Open circuit test voltage

> 4.0 V, < 8 V

Short circuit current

> 200.0 mA

Insulation Specifications

Measurement range

0.01 MΩ to 2000 MΩ

Test voltage

500 V, 1000 V

Test voltage accuracy

+ 20%, - 0%

Short circuit current

1 mA nominal

Auto discharge

Discharge time < 0.5 second for C = 1 µF or less

Live circuit indicator

Inhibit test if terminal voltage > 30 V prior to initialization of test

Maximum capacitive load

Operable with up to 1 µF load

Measure accuracy

500 V ±(1.5% + 5)
1000 V ±(1.5% + 5) to 2000 MΩ, ±(10% + 3) above 2000 MΩ

General Specifications

Maximum voltage applied to any terminal:

600 V AC rms or DC

Storage temperature

-40°C to 60°C (-40°F to 140°F)

Operating temperature

-20°C to 55°C (-4°F to 131°F)

Temperature coefficient

0.05 x (specified accuracy) per °C for temperatures < 18°C or > 28°C (< 64°F or > 82°F)

Relative humidity

0% to 95% @ 10°C to 30°C (50°F to 86°F)
0% to 75% @ 30°C to 40°C (86°F to 104°F)
0% to 40% @ 40°C to 55°C (104°F to 131°F)

Vibration

Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument

Shock

1 meter drop per IEC 61010-1 2nd Edition (1 meter drop test, six sides, oak floor)

Electromagnetic compatibility

In an RF field of 3 V/M, accuracy = specified accuracy (EN 61326-1:1997)

Safety

Complies with ANSI/ISA 82.02.01 (61010-1) 2004,
CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1
2nd Edition for measurement category IV 600 V (CAT IV)

Certifications

CSA per standard CSA/CAN C22.2 No. 61010.1-04;
TUV per standard IEC/EN 61010-1 2nd Edition

Batteries

Four AA batteries (NEDA 15A or IEC LR6)

Size (H x W x L)

5.0 x 10.0 x 20.3 cm (1.97 x 3.94 x 8.00 in)

Weight

550 g (1.2 lb)

IP rating

IP40

Altitude

Operating 2000 m CAT IV 600 V, 3000 m CAT III 600 V
Non-operating (storage) 12,000 m

Over-range capability

110% of range

Included accessories

TL224 Test Leads, TP74 Test Probes, clips PN 1958654 (red)
and PN 1958646 (black), holster and remote probe

Downloads

Datasheet : Fluke 1503 Insulation Resistance Meter

Instruction Manual : Fluke 1503 Insulation Resistance Meter