Dark Light
-17%
,

PQM-700 Power Quality Analysis

Availability:

2 in stock


 

  • 4 current inputs, physical measurement of current in the neutral conductor.
  • Registration of up to 1100 parameters, including average, maximum, minimum and instantaneous values.
  • Built-in heater, stable operation at low temperatures down to -20ºC.
  • Internal rechargeable battery, autonomy of the meter (min. 6 hours).
  • IP65 ingress protection, possibility of work in rain, snow and high humidity

158,000.00  190,000.00 

2 in stock

*

Product Description

Recording and diagnostics under all conditions

Resistant to any conditions, the Sonel PQM-700 power quality analyser is an effective device for analysing and recording network parameters. Based on advanced technology, the Sonel PQM-700 power quality analyser is effective for measuring, analysing and recording 50/60 Hz power network parameters. It is also used to control the quality of electricity in accordance with the European standard EN 50160 and the Regulation of the Minister of Economy of 4 May 2007 on detailed conditions for the operation of the power system. The extensive measurement capabilities of this device will be appreciated by a wide range of users who need a portable device to check the quality of electricity. The Sonel PQM-700 meets the demanding standards of the IEC 61000 standard for Class S analysers related to measurement uncertainties and measurement methods. This meter model is intended for those users who do not need a Class A analyser, as the PQM-700 provides comprehensive measurements of power quality parameters in Class S in accordance with IEC 61000-4-30.

Technical data

Parameters

Parameter

Measuring range

Max. resolution

Accuracy

Alternating voltage (TRMS)

-

0.0…760.0 V

4 significant digits

±0.5% Unom

Crest Factor

Voltage

1.00…10.00 (≤1.65 for 690 V voltage

0.01

±5%

Crest Factor

Current

1.00…10.00 (≤3.6 dla Inom)

0.01

±5%

Alternating current (TRMS)

-

depending on clamp*

4 significant digits

±0.2% Inom (error does not account for clamp error)

Frequency

-

40.00...70.00 Hz

0.01 Hz

±0.05 Hz

Active, reactive, apparent and distortion power

-

depending on configuration (transducers, clamps)

4 significant digits

depending on configuration (transducers, clamps)

Active, reactive and apparent energy

-

depending on configuration (transducers, clamps)

4 significant digits

as power error

cosφ and power factor (PF)

-

0.00...1.00

0.01

±0.03

tgφ

-

0,00...10,00

0.01

depends on error of active and reactive power

Harmonics

Voltage

DC, 1...40

as for alternating voltage True RMS

±0,15% Unom for m.v. < 3% Unom ±5% m.v. for m.v. ≥ 3% Unom

Harmonics

Current

DC, 1...40

as for alternating current True RMS

±0.5% Inom for m.v. < 10% Inom ±5% m.v. for m.v. ≥ 10% Inom

THD

Voltage and current

0.0..100.0% (relative to RMS value)

0.1%

±5%

Flicker index

-

0.40...10.00

0.01

±10%

Unbalance factor

Voltage and current

0.0...10.0%

0.1%

±0.3% (absolute error)

Downloads

Datasheet : PQM-700

Instruction Manual : PQM-700

 

Videos