MRP-201

Availability:

1 in stock


 

  • Testing of general, short delay and selective RCDs for the rated current values 10, 15, 30, 100, 300, 500 mA
  • Measurement of IA trip current and tripping time tA for currents 0.5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn
  • RE and UB measurement without RCD tripping
  • Extended AUTO function of RCD measurement
  • Measurement of IA and tA during one RCD tripping
  • Checking the correctness of PE connection using a contact electrode
  • Measurement of voltage (0 … 500 V) and network frequency
  • Memory of 990 results
  • Wireless data transmission to a computer

84,200.00  98,520.00 

1 in stock

*

Product Description

Specialist in residual current circuit breakers

The Sonel MRP-201 residual current circuit breaker meter is a specialist device for measuring all types of residual current circuit breakers – direct, short-delay, selective; types AC, A and B. It allows to measure tripping current, tripping time depending on differential current, resistance of protective conductor and contact voltage. Measurements can be performed individually or in series in automatic modes (all preset measurements for a given waveform or for all waveforms); simultaneous measurement of current and tripping time is also possible (with one RCD trip).

Technical data

Measurement functions

Measurement range

Display range

Resolution

Accuracy

Measurements of RCD parameters

RCD tripping test and measurement of tripping time tA measuring current 0.5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn

general and short-time delay RCD

0 ms…300 ms

0 ms…300 ms

1 ms

±(2% m.v. + 2 digits)

selective RCD

0 ms…500 ms

0 ms…500 ms

1 ms

±(2% m.v. + 2 digits)

Measurement of RCD tripping current IA measuring current 0.15 IΔn…2.0 IΔn

for sinusoidal residual current (AC type

3.0 mA…500 mA

3.0 mA…500 mA

from 0.1 mA

±5% IΔn

for unidirectional residual current and unidirectional with the 6 mA DC bias (type A)

1.5 mA…420 mA

1.5 mA…420 mA

from 0.1 mA

±10% IΔn

for direct residual current (type B)

2.0 mA…600 mA

2.0 mA…600 mA

from 0.1 mA

±10% IΔn

Voltage measurement

Abbreviation "m.v." used in the specification of measurement uncertainty means a standard measured value.

Range

Resolution

Accuracy

0.0 V... 299.9 V

0.1 V

±(2% m.v. + 6 digits)

300 V...500 V

1 V

±(2% m.v. + 2 digits)

Frequency measurement

Range

Resolution

Accuracy

45.0 Hz...65.0 Hz

0.1 Hz

±(0.1% m.v. + 1 digit)

Downloads