Dark Light
-32%
,

MIC-30 Insulation Resistance Meters

Availability:

4 in stock


 

  • Measurement of insulation resistance up to 100 GΩ thanks to max 1000 V measurement voltage
  • Designed for harsh environmental conditions conditions – IP67 ingress protection
  • Excellent for repeatable measurements – memory of 12,000 records and UNI-Schuko adapter for sockets
  • Allows for testing electrical continuity – RCONT 200 mA function
  • Checking start capacitors in motors thanks to capacity measurement function

46,000.00  67,200.00 

4 in stock

*

Product Description

Measure insulation resistance up to 100 GΩ

The Sonel MIC-30 insulation resistance meter is a perfect response to the expectations of users who deal with the testing of insulation of electrical installations in a repeated manner, e.g. in single- and multi-family buildings, as well as in public utility buildings and small plants and workshops. The device enables the setting of the measurement voltage within the range from 50 V to 1000 V in 10 V steps, which makes it perfect for diagnosing electrical, control, telecommunications and ICT facilities.

Technical data

Insulation resistance measurement

Measuring range:
Un=50 V: 50 kΩ…250.0 MΩ
Un=100 V: 100 kΩ…500.0 MΩ
Un=250 V: 250 kΩ…2.000 GΩ
Un=500 V: 500 kΩ…20.00 GΩ
Un=1000 V: 1000 kΩ…100.00 GΩ

Range

Resolution

Accuracy

0.0…999.9 kΩ

0.1 kΩ

± (3% m.v. + 8 digits) [± (5% m.v. + 8 digits)]*

1.000…9.999 MΩ

0.001 MΩ

± (3% m.v. + 8 digits) [± (5% m.v. + 8 digits)]*

10.00…99.99 MΩ

0.01 MΩ

± (3% m.v. + 8 digits) [± (5% m.v. + 8 digits)]*

100.0…250.0 MΩ (for Un = 50 V)

0.1 MΩ

± (3% m.v. + 8 digits) [± (5% m.v. + 8 digits)]*

100.0…500.0 MΩ (for Un = 100 V)

0.1 MΩ

± (3% m.v. + 8 digits) [± (5% m.v. + 8 digits)]*

100.0…999.9 MΩ (for Un ≥ 250 V)

0.1 MΩ

± (3% m.v. + 8 digits) [± (5% m.v. + 8 digits)]*

1.000…2.000 GΩ (for Un = 250 V)

0.001 GΩ

± (3% m.v. + 8 digits) [± (5% m.v. + 8 digits)]*

1.000…9.999 GΩ (for Un ≥ 500 V)

0.001 GΩ

±(4% m.v. + 6 digits) [±(6% m.v. + 6 digits)]*

10.00…20.00 GΩ (for Un ≥ 500 V)**

0.01 GΩ

±(4% m.v. + 6 digits) [±(6% m.v. + 6 digits)]*

10.00…99.99 GΩ (for Un = 1000 V)

0.01 GΩ

±(4% m.v. + 6 digits) [±(6% m.v. + 6 digits)]*

100.00 GΩ (for Un = 1000 V)

0.1 GΩ

±(4% m.v. + 6 digits) [±(6% m.v. + 6 digits)]*

Low-voltage measurement of continuity of circuit and resistance

Measuring range according to EN 61557-4: 0.10…1999 Ω

Range

Resolution

Accuracy

0.00…19.99 Ω

0.01 Ω

±(2% m.v. + 3 digits)

20.0…199.9 Ω

0.1 Ω

±(2% m.v. + 3 digits)

200…1999 Ω

1 Ω

±(2% m.v. + 3 digits)

DC and AC voltage measurement

Range

Resolution

Accuracy

0…299.9 V

0.1 V

±(2% m.v. + 6 digits)

300…600 V

1 V

±(2% m.v. + 2 digits)

Capacitance measurement

Range

Resolution

Accuracy

1…999 nF

1 nF

±(5% m.v. + 10 digits)

1.00…9.99 μF

0.01 μF

±(5% m.v. + 10 digits)

Low-current resistance measurement

Range

Resolution

Accuracy

0.00…199.9 Ω

0.1 Ω

±(3% m.v. + 3 digits)

200…1999 Ω

1 Ω

±(3% m.v. + 2 digits)

Downloads

Datasheet : MIC-30

Instruction Manual : MIC-30

Videos