  • Measurement voltage within the range of 100…2500 V, selected in steps of 100 V
  • Continuous reading of measured insulation resistance or leakage current
  • Automatic discharge of the measured object’s capacitance upon completion of insulation resistance measurement,
  • Sound signalling of five-second time intervals, facilitating capture of time characteristics
  • Timed measurement times T1 , T2 and T3 for measurement of absorption coefficients (Ab/PI/DAR) at 15, 60 and 600 s and polarization index
  • Reading of actual measurement voltage during measurement
  • Protection against measurement of live objects

72,500.00  94,000.00 

33 in stock

*

Product Description

Measure the insulation resistance up to 1 TΩ

The functional insulation resistance meter Sonel MIC-2501 surprises with numerous functions hidden in a neat and handy form. Due to its parameters, its robust casing with IP 65 protection level, its low battery power consumption and the possibility of recharging during measurements, the meter is a reliable tool that can be used in many areas. It is ideal for checking industrial installations and catenary networks, and is also successfully used in residential buildings. The advantages of this equipment are especially appreciated by electricians working in maintenance, testing motors, cables and street lighting. The Sonel MIC-2501 meter is also useful for measurements during construction and maintenance of photovoltaic installations. It is a reliable solution created for the needs of telecommunications network installers and heating network operators, facilitating the control of the alarm system of pre-insulated pipes.

Technical data

Insulation resistance measurement

Measurement range acc. to IEC 61557-2
for RISOmin = (UISOnom / IISOnom)…1 TΩ (IISOnom=1 mA)

Range

Resolution

Accuracy

0.0…999.9 kΩ

0.1 kΩ

± (3% m.v. + 20 digits)

1.000…9.999 MΩ

0.001 MΩ

± (3% m.v. + 20 digits)

10.00…99.99 MΩ

0.01 MΩ

± (3% m.v. + 20 digits)

100.0…999.9 MΩ

0.1 MΩ

± (3% m.v. + 20 digits)

1.000…9.999 GΩ

0.001 GΩ

± (3% m.v. + 20 digits)

10.00…99.99 GΩ

0.01 GΩ

± (3% m.v. + 20 digits)

100.0…999.9 GΩ

0.1 GΩ

± (3% m.v. + 20 digits)

1000 GΩ

1 GΩ

±(3% m.v. + 20 digits)

Low-voltage measurement of resistance and circuit continuity

Range

Resolution

Accuracy

0.00…19.99 Ω

0.01 Ω

±(2% m.v. + 3 digits)

20.0…199.9 Ω

0.1 Ω

±(2% m.v. + 3 digits)

200…999 Ω

1 Ω

±(2% m.v. + 3 digits)

DC and AC voltage measurement

Range

Resolution

Accuracy

0…299.9 V

0.1 V

±(3% m.v. + 2 digits)

300…750 V

1 V

±(3% m.v. + 2 digits)

Values of measured resistance depending on measurement voltage

Voltage UISO

Measurement range

up to 100 V

50 GΩ

200 V…400 V

100 GΩ

500 V…900 V

250 GΩ

1000 V…2400 V

500 GΩ

2500 V

1000 GΩ