  • HART® Protocol Compatibility: Supports HART® communication over the 4-20 mA current loop.
  • Electrical Isolation: Input and output are electrically isolated (1.5 kVrms).
  • Universal Sensor Input: Supports Thermocouples (J, K, R, S, T, N, E, B), RTDs (Pt100, Pt1000), NTC thermistors, and voltage (0-50 mV).
  • High Accuracy: ±0.15% of span for thermocouples, ±0.08% for Pt100.
  • Cold Junction Compensation: Improves thermocouple accuracy.
  • Remote Configuration: Configurable via SigNow software, TxConfig II software, or SigNow app.
  • Loop-Powered 4-20 mA Output: Provides linearized output proportional to input.
  • Fast Response Time: Typical response time of 6 seconds.
  • Wide Operating Temperature: -40 to 85 °C.
  • Compact Head-Mounted Design: Easily fits into sensor heads for industrial applications.

 

2,199.00  4,500.00 

33 in stock

*
Compare

Product Description

The resilience of NOVUS devices and the established quality of HART® certification are combined in the temperature transmitter TxIsoBlock-HRT. The transmitter supports voltage spikes up to 1.5 kVrms and offers electrical isolation between input and output. It is compatible with devices that have earned the HART® certification. The main difference is that it has two 4-20 mA current loop wires for total configuration, which means more functionality for monitoring and device setting.

 

NOVUS’s temperature transmitter TxIsoBlock-HRT uses a globally recognized protocol with over 40 million field instruments that accept HART® technology. This allows customers to have flexibility by using standard HART® configuration and supervision software.

A versatile head mount temperature transmitter that is essential to many industrial processes is the TxIsoBlock-HRT. It’s

The universal input can be set up to read mV signals, thermocouples, and RTDs.
In accordance with the specified range, it transforms the input signal into a linear output of 4–20 mA. TxIsoBlock-HRT communicates via the 4–20 mA output current loop using the HART® communication protocol.
Electrical isolation between the input and output improves both system and user safety.

Technical data

Specification

Input Type

J, K, T, N, R, S, B, E, Pt100, Pt1000, NTC and 0-50 mV

Accuracy Typical

Pt1000 / mV: 0.07 % span, Pt100: 0.08 % span, T/C: 0.07 % span ±1 °C (1.8 °F), NTC: 0.2 °C (0.36 °F)

Maximum

Pt1000 / mV: 0.15 % span , Pt100: 0.15 % span , T/C: 0.15 % span ±1 °C (1.8 °F) , NTC: 0.45 °C (0.81 °F)"

Output Type

4-20 mA

Output Resolution

0.25 µA

Thermal Drift

< 0.05 % / 25 °C (77 °F)

Isolation Input-Output

1.5 kVrms

Electric Protection

Reverse Polarity

HART® Version

HART V7, compatible with HART V5

Configuration Interface

Through TxConfig-HRT adapter or HART® certified HandHeld

Configuration Software

TxConfig II

Approvals / Regulations

CE, NAMUR NE43, RoHS, Reach, HART®

Operating Conditions

-40 to 85 °C (-40 to 185 °F) | 0 to 90% RH

Power Supply

4-20 mA Loop Powered (8.5 - 36 Vdc)

Enclosure

PA66

Format / Mounting

Head Mount

Downloads